EasyManua.ls Logo

Siemens SINAMICS S120 - Connection Diagram of the Power Module

Siemens SINAMICS S120
530 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G130
Engineering Information
SINAMICS Engineering Manual – November 2015
Ó Siemens AG
285/528
4.3 Connection diagram of the Power Module
An overview of the power and signal interfaces of the SINAMICS G130 Power Module is shown below.
Power connections
· Mains connection: U1, V1, W1, PE1
· Motor connection: U2, V2, W2, PE2
· DC link connection for optional braking unit: DCPA, DCNA
· DC link connection for optional dv/dt filter plus VPL or dv/dt filter compact plus VPL: DCPS, DCNS
Signal connections and 24 V auxiliary supply
· See connection diagram
1234
Control Interface Module CIM
56
DRIVE-CLiQ socket 0
-X400
DRIVE-CLiQ socket 1
-X401
DRIVE-CLiQ socket 2
-X402
Power Module
DCPS
DCNS
DCPA
DCNA
PE1
U1
V1
W1
PE2
U2
V2
W2
DRIVE-CLiQ socket
-X500
DRIVE-CLiQ sockets
-X500
DRIVE-CLiQ socket
-X100
DRIVE-CLiQ socket
-X500-X501
-X140 -X540
Serial interface
RS232
Serial interface
RS232
Control Unit
CU320-2
1st Terminal
Module TM31
Sensor Module
SMC30
Operator Panel
AOP30
2nd Terminal
Module TM31
[1] [2] [3] [4] [5] [6]
[1] Connection for an external
24 V supply
[2] Reserved
[3] Connection for controlling
a main contactor
[4] Connection for a temperature sensor
KTY84-130, PT1000, PT100 or PTC
for motor monitoring
[5] Connection for Safety Functions
Safe Torque Off / Safe Stop 1
[6] 24 V outgoing feeder to supply
the CU320-2 Control Unit and,
if installed, AOP30, TM31 and
SMC30
P24 M
[7]
[7] Connection for Safe Brake Adapter
Connection diagram for power and signal connections on the SINAMICS G130 Power Module

Table of Contents

Other manuals for Siemens SINAMICS S120