SINAMICS G130
Engineering Information
SINAMICS Engineering Manual – November 2015
Ó Siemens AG
285/528
4.3 Connection diagram of the Power Module
An overview of the power and signal interfaces of the SINAMICS G130 Power Module is shown below.
Power connections
· Mains connection: U1, V1, W1, PE1
· Motor connection: U2, V2, W2, PE2
· DC link connection for optional braking unit: DCPA, DCNA
· DC link connection for optional dv/dt filter plus VPL or dv/dt filter compact plus VPL: DCPS, DCNS
Signal connections and 24 V auxiliary supply
· See connection diagram
1234
Control Interface Module CIM
56
DRIVE-CLiQ socket 0
-X400
DRIVE-CLiQ socket 1
-X401
DRIVE-CLiQ socket 2
-X402
Power Module
DCPS
DCNS
DCPA
DCNA
PE1
U1
V1
W1
PE2
U2
V2
W2
DRIVE-CLiQ socket
-X500
DRIVE-CLiQ sockets
-X500
DRIVE-CLiQ socket
-X100
DRIVE-CLiQ socket
-X500-X501
-X140 -X540
Serial interface
RS232
Serial interface
RS232
Control Unit
CU320-2
1st Terminal
Module TM31
Sensor Module
SMC30
Operator Panel
AOP30
2nd Terminal
Module TM31
[1] [2] [3] [4] [5] [6]
[1] Connection for an external
24 V supply
[2] Reserved
[3] Connection for controlling
a main contactor
[4] Connection for a temperature sensor
KTY84-130, PT1000, PT100 or PTC
for motor monitoring
[5] Connection for Safety Functions
Safe Torque Off / Safe Stop 1
[6] 24 V outgoing feeder to supply
the CU320-2 Control Unit and,
if installed, AOP30, TM31 and
SMC30
P24 M
[7]
[7] Connection for Safe Brake Adapter
Connection diagram for power and signal connections on the SINAMICS G130 Power Module