EasyManua.ls Logo

Siemens SINAMICS S120 - Cable Cross-Sections and Connections on SINAMICS S150 Cabinet Units; Recommended and Max. Possible Cable Cross-Sections for Line and Motor Connections

Siemens SINAMICS S120
530 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS S150
Engineering Information
SINAMICS Engineering Manual – November 2015
Ó Siemens AG
486/528
8.4 Cable cross-sections and connections on SINAMICS S150 cabinet units
8.4.1 Recommended and max. possible cable cross-sections for line and motor connections
The following tables show the recommended and maximum connectable cable cross-sections on the line and motor
sides. The recommended cross-sections are based on the fuses specified in catalog D 21.3. These are valid for PVC-
insulated, copper 3-wire cables installed horizontally in air with a permissible conductor temperature of 70 °C (e.g.
Protodur NYY or NYCWY) at an ambient temperature of 40 °C and for singly routed cables. When the conditions
differ from the above stated (cable routing, cable grouping, ambient temperature), the relevant correction factors as
stated in IEC 60364-5-52 must be applied.
When aluminum cables are used, the recommended cross-sections given in the table must be increased by a factor
of 1.3. This can be done either by enlarging the conductor cross-section or by increasing the number of parallel
cables. It is important to note, however, that the cable cross-sections must not exceed the specified maximum
permissible dimensions at the converter and must be suitable for connection to the motor terminal box.
Out-
put
at
400 V
or
690 V
[kW]
Converter
SINAMICS
S150
Type
6SL3710-…
Weight
(stan-
dard
model)
[kg]
Line supply connection Motor connection Cabinet
grounding
Recommended
cross-section
1)
IEC
[mm
2
]
Maximum cable
cross-section
M12
fixing-
screw
(no. of
holes)
Recommended
cross-section
1)
IEC
[mm
2
]
Maximum cable
cross-section
M12
fixing
screw
(no. of
holes)
M12
fixing
screw
(no. of
holes)
Re-
marks
IEC
[mm
2
]
IEC
[mm
2
]
380 V – 480 V 3AC
110 7LE32-1AA3 708 2x70 4x240 (2) 2x50 2x150 (2) (2)
132 7LE32-6AA3 708 2x95 4x240 (2) 2x70 2x150 (2) (2)
160 7LE33-1AA3 892 2x120 4x240 (2) 2x95 2x150 (2) (2)
200 7LE33-8AA3 980 2x120 4x240 (2) 2x95 2x150 (2) (2)
250 7LE35-0AA3 980 2x185 4x240 (2) 2x150 2x240 (2) (2)
315 7LE36-1AA3 1716 2x240 4x240 (2) 2x185 4x240 (2) (2)
400 7LE37-5AA3 1731 3x185 4x240 (2) 2x240 4x240 (2) (10) Busbar
450 7LE38-4AA3 1778 4x150 8x240 (4) 3x185 4x240 (2) (16) Busbar
560 7LE41-0AA3 2408 4x185 8x240 (4) 4x185 6x240 (3) (18) Busbar
710 7LE41-2AA3 2408 4x240 8x240 (4) 4x240 6x240 (3) (18) Busbar
800 7LE41-4AA3 2408 6x185 8x240 (4) 6x185 6x240 (3) (18) Busbar
500 V – 690 V 3AC
75 7LG28-5AA3 708 50 4x240 (2) 35 2x70 (2) (2)
90 7LG31-0AA3 708 50 4x240 (2) 50 2x150 (2) (2)
110 7LG31-2AA3 708 70 4x240 (2) 70 2x150 (2) (2)
132 7LG31-5AA3 708 95 4x240 (2) 70 2x150 (2) (2)
160 7LG31-8AA3 892 120 4x240 (2) 95 2x150 (2) (2)
200 7LG32-2AA3 892 2x70 4x240 (2) 120 2x150 (2) (2)
250 7LG32-6AA3 892 2x95 4x240 (2) 2x70 2x185 (2) (2)
315 7LG33-3AA3 892 2x120 4x240 (2) 2x95 2x240 (2) (2)
400 7LG34-1AA3 1716 2x185 4x240 (2) 2x120 4x240 (2) (2)
450 7LG34-7AA3 1716 2x185 4x240 (2) 2x150 4x240 (2) (2)
560 7LG35-8AA3 1716 2x240 4x240 (2) 2x185 4x240 (2) (2)
710 7LG37-4AA3 2300 3x185 8x240 (4) 3x150 6x240 (3) (18) Busbar
800 7LG38-1AA3 2408 4x150 8x240 (4) 3x185 6x240 (3) (18) Busbar
900 7LG38-8AA3 2408 4x150 8x240 (4) 4x150 6x240 (3) (18) Busbar
1000 7LG41-0AA3 2408 4x185 8x240 (4) 4x185 6x240 (3) (18) Busbar
1200 7LG41-3AA3 2408 4x240 8x240 (4) 4x240 6x240 (3) (18) Busbar
1) The recommendations for the North American market in AWG or MCM can be found in the corresponding standards NEC
(National Electrical Code) or CEC (Canadian Electrical Code).

Table of Contents

Other manuals for Siemens SINAMICS S120