7.2.2.5 Cooling air requirements of air-cooled S120 Cabinet Modules
A specific quantity of cooling air must be supplied to air-cooled S120 Cabinet Modules. This volume of cooling air
must always be supplied, even under challenging boundary conditions. The cooling air is drawn in from the front
through the ventilation openings in the lower part of the cabinet doors. The heated air is expelled through the
perforated top cover or the ventilation openings in the top cover (with option M23/ M43/ M54). The minimum ceiling
height (for unhindered air outlet) specified in the dimension drawings must be observed. Cooling air can also be
supplied from below through raised floors or air ducts, for example. Openings in the 3-section baseplate must be
made for this purpose. Please also refer to the supplementary information for option M59 (Closed cabinet doors).
The tables below show the cooling air requirements of units in the Cabinet Modules range:
Line Connection Modules Cooling air requirement Line Connection Modules Cooling air requirement
Frame size I
rated
[A] [m³/s] Frame size I
rated
[A] [m³/s]
Supply voltage 380 V to 480 V 3AC Supply voltage 500 V to 690 V 3AC
FL 250 -
1
FL 280 -
1
FL
380
-
1
FL
380
-
1
GL
600
-
1
GL
600
-
1
HL
770
-
1
HL
770
-
1
JL
1000
0.36
1,
2
JL
1000
0.36
1,2
JL
1250
0.36
1,2
JL
1250
0.36
1,2
JL
1600
0.36
1,2
JL
1600
0.36
1,2
KL
2000
0.72
1,2
KL
2000
0.72
1,2
KL
2500
0.72
1,2
KL
2500
0.72
1,2
LL
3200
0.72
1,2
LL
3200
0.72
1,2
Basic Line Modules Cooling air requirement Basic Line Modules Cooling air requirement
Frame size
P
rated
at 400 V
[kW]
[m³/s]
Frame size
P
rated
at 690 V
[kW]
[m³/s]
Supply voltage 380 V to 480 V 3AC Supply voltage 500 V to 690 V 3AC
FB 200 0.17 FB 250 0.17
FB 250 0.17 FB 355 0.17
FB 400 0.17 FB 560 0.17
GB 560 0.36 GB 900 0.36
GB 710 0.36 GB 1100 0.36
GD 900 0.36 GD 1500 0.36
Smart Line Modules Cooling air requirement Smart Line Modules Cooling air requirement
Frame size
P
rated
at 400 V
[kW]
[m³/s]
Frame size
P
rated
at 690 V
[kW]
[m³/s]
Supply voltage 380 V to 480 V 3AC Supply voltage 500 V to 690 V 3AC
GX 250 0.36 GX 450 0.36
GX 355 0.36 HX 710 0.78
HX 500 0.78 JX 1000 1.08
JX 630 1.08 JX 1400 1.08
JX 800 1.08
Active Line Module +
Active Interface Module
Cooling air requirement
Active Line Module +
Active Interface Module
Cooling air requirement
Frame size
P
rated
at 400 V
[kW]
[m³/s]
Frame size
P
rated
at 690 V
[kW]
[m³/s]
Supply voltage 380 V to 480 V 3AC Supply voltage 500 V to 690 V 3AC
FI+FX 132 0.47 HI+HX 630 1.18
FI+FX 160 0.47 JI+JX 800 1.48
GI+GX 235 0.83 JI+JX 1100 1.48
GI+GX 300 0.83 JI+JX 1400 1.48
HI+HX 380 1.18
HI+HX 500 1.18
JI+JX 630 1.48
JI+JX 900 1.48
1
Components use natural convection
2
Fan for degree of protection IP23, IP43, IP54 (in combination with Basic Line Modules)