Parameter list
8.2 Parameter list
SINAMICS V20 Converter
Operating Instructions, 10/2019, A5E34559884-012
225
Function of digital input 4
Selects function of digital input 4.
See P0701.
Function of digital input 5
Selects function of digital input 5.
This digital input is provided by the optional I/O Extension Module.
Function of digital input 6
Selects function of digital input 6.
This digital input is provided by the optional I/O Extension Module.
Selects function of digital input AI1 (via analog input).
See P0701. Signals above 4 V are active; signals below 1.6 V are inactive.
Selects function of digital input AI2 (via analog input).
See P0701. Signals above 4 V are active; signals below 1.6 V are inactive.
Selects a given connection macro, which is a set of parameter values for a given set of control connec-
tions. There are a number of connection macros which define basic control connection settings such as
Terminals, BOP, PID with analog setpoint etc.
Please note that to guarantee correct setting of the Connection macro, the Connection macro number
should only be changed during Setup directly after a parameter reset.
P0719[0...2]
Selection of command &
frequency setpoint
0 - 57 0 T - CDS U16 4
Central switch to select control command source for converter. Switches command and setpoint source
between freely programmable BICO parameters and fixed command/setpoint profiles. Command and
setpoint sources can be changed independently. The tens digit chooses the command source and the
units digit chooses the setpoint source.
Cmd = BICO parameter, Setpoint = BICO parameter
Cmd = BICO parameter, Setpoint = MOP setpoint
Cmd = BICO parameter, Setpoint = Analog setpoint
Cmd = BICO parameter, Setpoint = Fixed frequency
Cmd = BICO parameter, Setpoint = USS on RS232 (reserved)
Cmd = BICO parameter, Setpoint = USS/MODBUS on RS485
Cmd = BICO parameter, Setpoint = Analog setpoint 2
Cmd = USS on RS232 (reserved), Setpoint = BICO parameter
Cmd = USS on RS232 (reserved), Setpoint = MOP setpoint
Cmd = USS on RS232 (reserved), Setpoint = Analog setpoint
Cmd = USS on RS232 (reserved), Setpoint = Fixed frequency
Cmd = USS on RS232 (reserved), Setpoint = USS on RS232 (reserved)