Parameter list
8.2 Parameter list
SINAMICS V20 Converter
226 Operating Instructions, 10/2019, A5E34559884-012
Cmd = USS on RS232 (reserved), Setpoint = USS/MODBUS on RS485
Cmd = USS on RS232 (reserved), Setpoint = Analog setpoint 2
Cmd = USS/MODBUS on RS485, Setpoint = BICO parameter
51 Cmd = USS/MODBUS on RS485, Setpoint = MOP setpoint
Cmd = USS/MODBUS on RS485, Setpoint = Analog setpoint
Cmd = USS/MODBUS on RS485, Setpoint = Fixed frequency
Cmd = USS/MODBUS on RS485, Setpoint = USS on RS232 (reserved)
Cmd = USS/MODBUS on RS485, Setpoint = USS/MODBUS on RS485
Cmd = USS/MODBUS on RS485, Setpoint = Analog setpoint 2
P0719 has higher priority than P0700 and P1000. If set to a value other than 0 (i.e. BICO parameter is not
the setpoint source), P0844/P0848 (first source of OFF2/OFF3) are not effective; instead, P0845/P0849
(second source of OFF2/OFF3) apply and the OFF commands are obtained via the particular source
defined. BICO connections made previously remain unchanged.
Particularly useful when e.g. changing command source temporarily from P0700 = 2. Settings in P0719
(contrary to P0700 settings) do not reset the digital inputs (P0701, P0702, ...)
Displays number of digital inputs.
r0722.0...12
CO/BO: Digital input
values
- - - - - U16 2
Displays status of digital inputs.
Segment is lit when signal is active.
The digital input 5 and 6 are provided by the optional I/O Extension Module.
P0724
Debounce time for digital
inputs
0 - 3 3 T - - U16 3
Defines debounce time (filtering time) used for digital inputs.