Parameter list
8.2 Parameter list
SINAMICS V20 Converter
228 Operating Instructions, 10/2019, A5E34559884-012
•
using STOP as permanent signal, FWD and REVP as pulses
•
using OFF1/HOLD and REV as permanent signal, ON as pulse signal
Where:
• P denotes Pulse
• FWD denotes FORWARD
• REV denotes REVERSE
When any of the control functions are selected using P0727, the setting for the digital inputs (P0701 -
P0704) are redefined as follows:
Settings of
P0727 = 0 (Siemens
P0727 = 1 (2-
P0727 = 2 (3-wire
P0727 = 3 (3-wire
To use the 2/3-wire control, the sources for ON/OFF1 (P0840), ON_REV/OFF1 (P0842) and REV (P1113)
corresponding to the redefined values have to be set accordingly.
The ON/OFF2 functionality is not supported in 2/3 wire modes. Do not select ON/OFF2 unless P0727 = 0.
Regarding the use of fixed frequencies see P1000 and P1001.