Electrical installation
4.2 Terminal description
SINAMICS V20 Converter
44 Operating Instructions, 10/2019, A5E34559884-012
User terminals
The illustration below takes the user terminal layout for FSA to FSE for example.
1 10V 10 V output (tolerance ± 2% for the temperature range of 20 °C to 30 °C) referred to
0V, maximum 11 mA, short circuit protected
2
3
AI1
AI2
Mode: AI1: Single-ended, bipolar current and voltage
mode
AI2: Single-ended, unipolar current and voltage
Isolation to control circuit:
AI1: -10 V to 10 V; AI2: 0 V to 10 V
Current range: 0 mA to 20 mA (4 mA to 20 mA - software se-
Voltage mode accuracy: ± 1% full scale for the temperature range of
Current mode accuracy: ± 1% full scale for the temperature range of
Input impedance: Voltage mode: > 30 K
Threshold 0 ⇒ 1 (used as DI):
Threshold 1 ⇒ 0 (used as DI):
Response time (digital input mode):
4 AO1
Single-ended, unipolar current mode
Isolation to control circuit:
0 mA to 20 mA (4 mA to 20 mA - software selectable)
Accuracy (0 mA to 20 mA): ± 0.5 mA for the temperature range of -10 °C to
Overall reference potential for RS485 communication and analog inputs/output