Parameter Value
SENTRON PAC3200 SENTRON PAC4200
Measuring inputs for voltage
3 AC; UL-L/UL-N; CAT III
● Wide-range power supply
Max. 690 V / 400 V
95 to 240 VAC 50/60 Hz ±10%
110 to 340 VDC ±10%
Measuring inputs for voltage
3 AC; UL-L/UL-N; CAT III
● Low-voltage power supply
Max. 500 V / 289 V
22 to 65 VDC; ±10%
Measurement at voltage transformers for
voltages > 500 V / 690 V
✓ ✓
Measuring inputs for current
3 AC; CAT III
x/1 A or x/5 A
Current direction
programmable
✓ ✓ per phase
Measurement using current transformers ✓ ✓
Dimensions (W x H x D) 96 x 96 x 56 mm 96 x 96 x 82 mm
Overall depth
● Without module
● With module
51 mm
73 mm
77 mm
99 mm
Protection class II
Degree of protection at front IP65
Slots for expansion modules 1 2
Operating temperature -10 to +55° C
Relative humidity in operation
at 25° C without condensation
95 %
Degree of contamination 2
Approvals CE, cULus, C-Tick, GOST CE, cULus, GOST
Further information
You can find additional information on the Internet at:
● SENTRON PAC3200 (http://support.automation.siemens.com/WW/view/de/25240652)
● SENTRON PAC4200 (http://support.automation.siemens.com/WW/view/de/31675630)
Spare parts and accessories
9.3 SENTRON PAC3200/PAC4200
PPU
234 Manual, 01/2014, 6FC5397-2DP40-3BA3