1356* Stop C triggered Reset key
After selection of SG, SE
Interlocking of NC START
Follow–up mode for all axes of this mode group
Removal of Mode Group Ready
Interruption of machining
This alarm occurs with the alarms ”safe speed exceeded” or ”safe position exceeded” (when configured accord-
ingly in MD 4508* Bit 4: (STOP D/E selection for SG) or MD 4508* Bit 2: (STOP D/E selection for SE). It indicates
the initiation of ”braking at the current limit” and the internal activation of the ”safe standstill”.
Remedy the causes of ”safe speed exceeded” or ”safe end position exceeded” (see description of the alarms).
Remedy the error and press the RESET key (the program is aborted and must be restarted).
Applies as from SW 5.4.
1360* Stop B triggered POWER ON
After selection of SG, SE after selection of SBH
After initiation of STOP C, D, E
After initiation of STOP F and activated SBH/SG or SE, SN
Interlocking of NC START
Follow–up mode for all axes of this mode group
Removal of Mode Group Ready
Interruption of machining
Pulse deletion after timer expires (SGA)
This alarm occurs with the alarm ”tolerance for safe standstill exceeded” or alarm ”STOP F triggered”. It indicates
the initiation of ”braking at the current limit” and the internal activation of the timer for switchover to STOP A (see
MD 4268*: (pulse deletion delay time).
Remedy the causes of ”tolerance for safe standstill exceeded” or for ”STOP F triggered” (see description of the
alarms).
Not possible. Acknowledgement of the alarm only possible by POWER ON.
Applies as from SW 5.4.
1364* Stop A triggered POWER ON
After selection of SBH
After initiation of STOP B
Interlocking of NC START
Removal of Mode Group Ready
Interruption of machining
Immediate pulse deletion (SGA)
This alarm occurs with the alarm ”tolerance for safe standstill exceeded” or as a result of STOP B or an unsuc-
cessful test stop. It indicates the initiation of a ”pulse deletion”.
Remedy the causes of ”tolerance for safe standstill exceeded” or for ”STOP F triggered” (see description of the
alarms).
Not possible. Acknowledgement of the alarm only possible by POWER ON.
Applies as from SW 5.4.
1368* Protection zone collision plus RESET
Cyclic with active function ”Collision monitoring”
Axis number
Machining standstill;
disabling of NC Start
Overlap of two protection zones has been recognized
Travel free and trigger mode group reset
Applies as from SW 6.
Scan
Effect
Explanation
Remedy
Continuation
Note
Scan
Effect
Explanation
Remedy
Continuation
Note
Scan
Effect
Explanation
Remedy
Continuation
Note
Scan
Parameters
Effect
Explanation
Remedy
Note