203
Group Switchover of the Function Parameters
IEC 61850 GOOSE (Inter-Relay Communication)
Number of available setting groups 4 (parameter group A, B, C and D)
Switchover can be performed via the keypad on the device
DIGSI using the operator interface
protocol using port B
binary input
The GOOSE communication service of IEC 61850 is qualified for switchgear interlocking. Since the transmis-
sion time of GOOSE messages depends on both the number of IEC 61850 clients and the relay's pickup con-
dition, GOOSE is not generally qualified for protection-relevant applications. The protective application is to
be checked with regard to the required transmission time and cleared with the manufacturer.