EasyManuals Logo

Siemens SIPROTEC 7RW80 User Manual

Siemens SIPROTEC 7RW80
260 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
Introduction
1.3 Characteristics
SIPROTEC, 7RW80, Manual
C53000-G1140-C233-1, Release date 10.2010
21
Load Restoration
4 separately adjustable load restoration stages
Individually assignable low frequency stages, which start the load restoration stage (1 to 4 for each load
restoration stage)
Settable dropout ratio for all stages of the load restoration
Monitoring of the settable restoration cycles (no ON/OFF chattering)
Monitoring Functions
Reliability of the device is greatly increased because of self-monitoring of the internal measurement circuits
as well as the hardware and software.
Monitoring the secondary circuits of voltage transformers via summation and symmetry control techniques
with optional blocking of protection function.
Broken-wire Monitoring of Voltage Transformer Circuits
Trip circuit monitoring
Phase rotation check.
Flexible Protective Functions
Up to 20 protection functions which can be set individually to operate in three-phase or single-phase mode
Any calculated or directly measured value can be evaluated on principle
Standard protection logic with a constant (i.e. independent) characteristic curve
Internal and configurable pickup and dropout delay
Modifiable message texts.
Synchrocheck
Check of the synchronism conditions or de-energized state before manual closing of the circuit breaker
Fast measurement of the voltage difference ΔV, the phase angle difference Δϕ and the frequency difference
Δf
Adjustable minimum and maximum voltage;
Measurement also possible via transformer without external intermediate matching transformer
Measuring voltages optionally phase–to–phase or phase–to–ground.
Overecxitation Protection
Calculation of the V/f ratio.
Adjustable warning and tripping stage.
Standard characteristic or arbitrary trip characteristic selectable for calculation of the thermal stress.
Jump of Voltage Vector
Sensitive phase jump detection to be used for network disconnection.