EasyManua.ls Logo

Siemens siprotec 7SJ63 - Page 115

Siemens siprotec 7SJ63
604 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuration
5-37SJ63 Manual
C53000-G1140-C120-1
Figure 5-1 Device Configuration Dialog Box in (example) DIGSI
®
4
Before closing the dialog box, transfer the modified functional setting to the relay by
clicking on the item ',*6, 'HYLFH. The data is stored in the relay in a Non-Volatile
Memory Buffer.
The configured functional scope can be
viewed
from the front display of the relay itself,
but cannot be modified. The settings associated with the functional scope can be
found in the 0$,10(18 under 6HWWLQJV 'HYLFH&RQILJ.
Special Character-
istics
If use of the setting group change function is desired, address  should be set to
(QDEOHG. In this case, up to four different groups of settings (see Chapter 6) may be
entered quickly and easily during device operation. Only one setting group may be se-
lected and used if the setting is 'LVDEOHG.
For the relay elements associated with non-directional overcurrent protection (both
phase and ground ), various tripping characteristics may be selected at the addresses
 (phase) and  (ground). If only the definite time characteristic is desired,
then 'HILQLWH7LPHRQO\
should be selected. Additionally, depending on the relay
model ordered, various inverse time characteristics are available (based on either IEC
standards or ANSI standards), or user defined characteristics may be specified. A
user defined characteristic can include both a tripping and a reset characteristic. Non-
directional overcurrent protection may be defeated during configuration by selecting
'LVDEOHG.
For directional overcurrent protection, the same information can be entered at ad-
dresses  (phase) and  (ground) that was entered for the non-directional
overcurrent protection at addresses  and .
For sensitive ground fault protection, address  is used to specify whether the
function should be disabled, enabled with definite time tripping characteristics only, or
enabled with a user defined inverse time characteristic.
For negative sequence protection, address  is used to specify whether the func-
tion should be disabled, enabled with definite time tripping characteristics only, or en-
abled with an ANSI inverse time characteristic.
For trip circuit monitoring, address  7ULS&W6XSY is used to specify wheth-
er two binary inputs should be utilized, one binary input should be utilized, or the func-
tion should be disabled.
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens siprotec 7SJ63

Related product manuals