Appendix
A-1017SJ63 Manual
C53000-G1140-C120-1
A.9.2 Pre-Defined CFC Charts
Some CFC Charts are already supplied with the SIPROTEC
®
device:
Device and System
Logic
:
Figure A-44 Device and System Logic
Set points Using modules on the running sequence “measured value processing”, a low current
monitor for the three phase currents is implemented. The output message is set high
as soon as one of the three phase currents falls below the set threshold:
Figure A-45 Undercurrent monitoring
IN: Device,
OUT: Control Device Block Data IntSP
IN: Control Device
OUT: Device, General Feeder gnd IntSP
General SP
GndSwit. DP
OUT: Device, General Brk OPENEDIntSP
IN: Device,
52 Breaker DP
IN: Data 2 Relay
TRIP OUT
IN: Set points 37-1 LV
IN: Measurement Ia = MV
IN: Set points 37-1 LV
IN: Measurement Ib = MV
IN: Set points 37-1 LV
IN: Measurement Ic = MV
OUT: Set points SP. 37-1
alarm OUT