SIPROTEC 4 Devices
4-10 7SJ63 Manual
C53000-G1140-C120-1
4.3.1 Annunciations
The scope of the indication (messages) that are given under Annunciation is automat-
ically determined when settings for the basis configuration of functions are applied to
the SIPROTEC
®
4 device.
The messages are divided into the following categories, and displayed using DIGSI
®
4
or the HMI of the device:
q
Event Log: Operational messages independent of network faults, e.g. messages
about control operations or monitoring functions;
q
Trip Log: Fault messages;
q
Sensitive Ground Fault Log: Ground fault messages for devices with sensitive
ground fault detection;
q
General Interrogation: Display of present condition messages;
q
Spontaneous Annunciation: Continuous display of important messages from the
device; e.g., after faults, control operations, etc. This feature is very helpful during
commissioning.
k451.gif
Figure 4-3 DIGSI
®
4, Annunciation
Display in DIGSI
®
4 To view the indications in the DIGSI
®
4 Tool 2QOLQH:
Select $QQXQFLDWLRQ in the navigation window.
All annunciation groups are shown in the data window.
Double click on an annunciation group in the data window, such as (YHQW/RJ.
The data and time appear. Double click on the entry. The list of indications appears.
Display on
the Device
To display messages in the HMI of the SIPROTEC
®
4 device: