7-97SJ63 Manual
C53000-G1140-C120-1
Use the and keys to view the messages for a fault.
Use the key to move back into the *5281')$8/7/2* sub-menu; the key to
go back to the 0$,10(18.
From PC with
DIGSI
®
4
Click on $QQXQFLDWLRQ. The options appear in the data window (see Figure 7-2).
Double click on the desired message group, in this case *URXQG)DXOW/RJ. A list
appears in the data window, as shown in Figure 7-10.
By double clicking on an entry in the list view, the associated contents of the ground
fault record are displayed in another window, as shown in Figure 7-11.
Figure 7-10 DIGSI
®
4 Selection of Ground Fault Log with a Fault Indicated in the Data Win-
dow
Figure 7-11 DIGSI
®
4 Example of Indications for a Ground Fault, Ground Fault Log
7.1.1.5 Saving and Erasing the Messages
Normally, erasing the messages is not necessary because the oldest messages are
automatically erased when new events are entered, if the memory is full at the time.
However, erasure of the stored messages may be useful, for instance, after revision
or commissioning, so that in the future the memory only contains information about ac-
tual events. Erasing the memory takes place separately for each of the Fault Logs.