EasyManua.ls Logo

Siemens siprotec 7SJ63 - Waveform Capture

Siemens siprotec 7SJ63
604 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
6-1697SJ63 Manual
C53000-G1140-C120-1
Minimum and maximum values for the above mentioned long-term averages, in-
cluding the date and time they were last updated, in primary values.
Real and reactive energy flow (including direction of flow) in kWh, MWh, or GWh
primary; or in kVArh, MVArh, or GVArh primary.
−Θ/Θ
out
overload protection values for stator and rotor in % of the trip initiating ex-
cessive temperature,
I
Greal
and I
Greactive
real and reactive components of the sensitive ground current de-
tection as secondary quantities in mA.
The measured values are updated at a period of 0.3 s and 1 s.
The minimum and maximum values are listed with the date and time of the latest up-
date. Using binary inputs or a SCADA interface, the maximum and minimum values
can be reset. In addition, the reset can also take place cyclically, beginning with a pre-
selected point in time.
For the long-term averages mentioned above, the length of the time window for aver-
aging and the frequency with which it is updated can be set. The associated minimum
and maximum values can be reset, using binary inputs or by using the integrated con-
trol panel in the DIGSI
®
4 operating program.
Transfer of
Measured Values
Measured values can be retrieved by SCADA, or through DIGSI
®
4.
Set points To recognize extraordinary operational conditions, warning levels can be pro-
grammed. When a programmed limit value is exceeded (or fallen below), a message
is generated that can be masked to both output relays and LEDs. In contrast to the
actual protective functions, such as time-overcurrent protection or overload protection,
this monitoring program may becomes lower.
The following individual limit value levels are configured, when delivered from factory:
Falling below a preset current in any phase
Exceeding a preset maximum average current in Phase A
Exceeding a preset maximum average current in Phase B
Exceeding a preset maximum average current in Phase C
Exceeding a preset maximum average positive sequence current
Exceeding a preset maximum average real power
Exceeding a preset maximum average reactive power
Exceeding a preset maximum average apparent power
Falling below a preset power factor
6.19.3 Waveform Capture
The 7SJ63 relay is equipped with an oscillographic data saving feature. The momen-
tary values for the measurement quantities
I
a
, I
b
, I
c
, I
G
, and I
Ns
, and V
a
, V
b
, V
c
, 3V
0
(voltages depending on the connection) are scanned at intervals of 1.04 ms for 60 Hz
(1.25 ms for 50 Hz) and stored in a revolving buffer (16 samples per cycle). For a fault,
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens siprotec 7SJ63

Related product manuals