Operators Tools
7-437SJ63 Manual
C53000-G1140-C120-1
Figure 7-48 Manual Overwriting for Switching Devices from the Front Panel
By pressing the key, a selection window is opened for the marked switch, in
which manual overwriting can be done with the options 23(1&/26(. See Figure 7-
49.
Make the selection using the and keys, and confirm with the key.
Enter Password No. 2 (for non-interlocked switching) and acknowledge with the
key.
Figure 7-49 Selection Window for Manual Overwriting of a Switch Position, Front Panel
A safety inquiry appears: “$UH\RXVXUH"” Provided manual overwriting is allowed,
a response of “<(6” results in an appropriate message on the display. Acknowledge
the message by pressing the key again.
Manual overwriting is cancelled if the process is restricted because, for example, “LQ
SXWLJQRUHG” is not set (see Sub-section 7.3.3). Manual overwriting is also canceled
if the user aborts the procedure. The display provides an appropriate message if man-
ual overwriting is canceled. Acknowledge the message by pressing the key.
Return to the %5($.(56:,7&+ sub-menu using the key, or the 0$,10(18 by
pressing the key.
From PC with
DIGSI
®
4
For safety reasons, manual overwriting is only possible locally using the keypad on the
front panel of the device. The feature is not available in DIGSI
®
4.
7.3.3 Set Status
A feature of the 7SJ63 that is especially useful during testing and commissioning of
the device is the capability of temporarily removing the coupling between a switching
device and the 7SJ63, or between the SCADA and the 7SJ63, without physically dis-
connecting the equipment. This type of separation is also necessary, for instance, if a
switch position feedback message is not functioning properly (refer to Sub-section
7.3.2). The menu item 6(767$786 is used to perform the decoupling.
%5($.(56:,7&+

'LVSOD\³!
&RQWURO²!
!0DQ2YHUZULWH²!
6HWVWDWXV³!
0$129(5:5,7(

%UHDNHU!23(1
'LVF6ZLW&/26
*QG6ZLW23(1
ENTER
ENTER
ENTER
0$12
!23(1
!%UH&/26!23(1
!'LVF&/26
ENTER
ENTER
MENU
: