Operators Tools
7-44 7SJ63 Manual
C53000-G1140-C120-1
The menu displays a list of all planned switching devices and associated status infor-
mation identified by a letter. The letters have the following meanings:
• T Device is tagged (manually overwritten).
• I Input ignored, which means the acquisition of an input status is de-coupled from
the process (from the switch-gear).
• B Blocked, which means data transmissions to the central device (or SCADASCA-
DA) are blocked.
• C Chatter block active, which means, because of frequent message changes, the
chatter block was set.
• O Output block active, which means the command output is de-coupled from the
process (from the system).
• – None of the listed limitations is in effect.
From the
Device Front
With a device ready for operation, first press the key. The 0$,10(18 appears.
Using the key, select the menu item &RQWURO and go to editing the control func-
tions with the key. The selection &21752/ appears.
Enter the %5($.(56:,7&+ menu by pressing the key.
Select the item 6HW6WDWXV with the key and switch to the next option using the
key. 6(767$786 appears, as shown in Figure 7-50.
Figure 7-50 Set Status at the Front Panel
Move the cursor, using the and keys, to each of the second (Input Ignore) and
fifth (Control Block) columns of the switching device for which a status change is de-
sired. Entries in this table can only be made in these two columns.
Press the key. A selection window is opened that displays the meaning of the
field and the change options that are available.
Note:
Input ignored only works for physical inputs! Do not set the block for indications cre-
ated by CFC.
MENU
1. 2. 3. 4. 5.
Column
%5($.(56:,7&+
'LVSOD\³!
&RQWURO²!
!0DQ2YHUZULWH²!
!6HWVWDWXV³!
6(767$786
%UHDNHU7,2
'LVF6ZLW!
*QG6ZLW
ENTER
www . ElectricalPartManuals . com