Functions
6-677SJ63 Manual
C53000-G1140-C120-1
1905 51Nc PICKUP 0.50 ~ 20.00 A 5.00 A 1307 51N PICKUP X X X X
1906 51Nc T-DIAL 0.05 ~ 3.20 sec. 0.50 sec. 1308 51N TIME DIAL, IEC X X X
1907 51Nc T-DIAL 0.5 ~ 15.00 5.00 1309 51N TIME DIAL, ANSI X
Addr. Setting Setting Options Default
Setting
Addr. Normal Setting Configuration
Definite Time Only
IEC Curve
ANSI Curve
User Defined Pickup
User def. Reset
2001 67c-2 PICKUP 0.50 ~ 175.00 A 50.00 A 1502 67-2 PICKUP X X X X X
2002 67c-2 DELAY 0.00 ~ 60.00 sec. 0.00 sec. 1503 67-2 DELAY X X X X X
2003 67c-1 PICKUP 0.50 ~ 175.00 A 10.00 A 1504 67-1 PICKUP X X X X X
2004 67c-1 DELAY 0.00 ~ 60.00 sec. 0.30 sec. 1505 67-1 DELAY X X X X X
2005 67c-TOC PICKUP 0.50 ~ 20.00 A 7.50 A 1507 67-TOC PICKUP X X X X
2006 67c-TOC T-DIAL 0.05 ~ 3.20 sec. 0.50 sec. 1508 67-TOC TIME DIAL, IEC X X X
2007 67c-TOC T-DIAL 0.5 ~ 15.00 5.00 1509 67-TOC TIME DIAL, ANSI X
Addr. Setting Setting Options Default
Setting
Addr. Normal Setting Configuration
Definite Time Only
IEC Curve
ANSI Curve
User Defined Pickup
User def. Reset
2101 67Nc-2 PICKUP 0.25 ~ 175.00 A 35.00 A 1602 67N-2 PICKUP X X X X X
2102 67Nc-2 DELAY 0.00 ~ 60.00 sec. 0.00 sec. 1603 67N-2 DELAY X X X X X
2103 67Nc-1 PICKUP 0.25 ~ 175.00 A 7.50 A 1604 67N-1 PICKUP X X X X X
2104 67Nc-1 DELAY 0.00 ~ 60.00 sec. 0.30 sec. 1605 67N-1 DELAY X X X X X
2105 67Nc-TOC PICKUP 0.50 ~ 20.00 A 5.00 A 1607 67N-TOC PICKUP X X X X
2106 67Nc-TOC T-DIAL 0.05 ~ 3.20 sec. 0.50 sec. 1608 67N-TOC T–DIAL, IEC X X X
2107 67Nc-TOC T-DIAL 0.5 ~ 15.00 5.00 1609 67N-TOC T–DIAL, ANSI X
Addr. Setting Setting Options Default
Setting
Addr. Normal Setting Configuration
Definite Time Only
IEC Curve
ANSI Curve
User Defined Pickup
User def. Reset
www . ElectricalPartManuals . com