EasyManua.ls Logo

Siemens siprotec 7SJ63 - Page 248

Siemens siprotec 7SJ63
604 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
6-84 7SJ63 Manual
C53000-G1140-C120-1
1
) if address 0213: Vab, Vbc, VGnd
2
) if address 0213: Van, Vbn, Vcn
3106 VPH MIN 10 ~ 100 V 40 V Voltage of faulty phase Vph min X X
3107 VPH MAX 10 ~ 100 V 75 V Voltage of
Unfaulted phase
Vph max
XX
3109
64-1 VGND
1
)
1.8 ~ 130.0 V 40.0 V
64-1 Ground Displacement Voltage X X
3110
64-1 VGND
2
)
10.0 ~ 225.0 V 70.0 V
64-1 Ground Displacement Voltage X X
3111 T-DELAY
Pickup.
0.4 ~ 320.00 sec 1.00 sec
Time-DELAY Pickup X X
3112
64-1 DELAY
0.10 ~ 40000.0 sec 10.00 sec
64-1 Time Delay X X
3113
50Ns-2 PICKUP
0.003 ~ 1.500 A 0.300 A
50Ns-2 Pickup X X
3114
50Ns-2 DELAY
0.00 ~ 320.00 sec 1.00 sec
50Ns-2 Time Delay X X
3115
67Ns-2 DIRECT.
Forward
Reverse
Non-Directional
Forward
67Ns-2 Direction X X
3117
50Ns-1 PICKUP
0.003 ~ 1.500 A 0.100 A
50Ns-1 Pickup X
3118
50Ns-1 DELAY
0.00 ~ 320.00 sec 2.00 sec
50Ns-1 Time delay X
3119
51Ns PICKUP
0.003 ~ 1.400 A 0.100 A
51Ns Pickup X
3120
51Ns TIME DIAL
0.10 ~ 4.00 sec 1.00 sec
51Ns Time Dial X
3122
67Ns-1 DIRECT. Forward
Reverse
Non-Directional
Forward 67Ns-1 Direction X X
3123
RELEASE
DIRECT.
0.003..1.200 A 0.010 A Release directional element X X
3124
PHI CORREC-
TION
-45.0..45.0 ° 0.0 ° Correction Angle for Dir. Determina-
tion
XX
3125
MEAS. METHOD COS Phi
SIN phi
COS Phi Measurement method for Direction X X
3126
RESET DELAY 0..60 sec 1 sec Reset Delay X X
3130
PU CRITERIA Vgnd OR INs
Vgnd AND INs
Vgnd OR INs Sensitive Ground Fault PICKUP crite-
ria
XX
3131
M.of PU TD Multiples of PU Time-Dial X
Addr. LCD-Text Setting options Default Setting Comment Configu-
ration
Definite Time only
User Defined Pickup
www . ElectricalPartManuals . com