7-18 7SJ63 Manual
C53000-G1140-C120-1
device and possibly nominal data settings entered (ad-
dresses 935,0$5<23, ,35,0$5<23,
refer subsection 6.1.3)
6. 'HPDQG Long-term average, in primary quantities.
The measured values are converted from secondary to pri-
mary according to the settings entered for the current and
voltage transformers, and the nominal device values.
7. 0LQ0D['HPDQG Minimum and maximum of the averages, with the date and
time that they occurred, in primary quantities.
The measured values are converted from secondary to pri-
mary according to the settings entered for the current and
voltage transformers, and the nominal device values.
8. 9,0LQ0D[ Minimum and maximum of the voltages and currents, with
the date and time that they occurred, in primary quantities.
The measured values are converted from secondary to pri-
mary according to the settings entered for the current and
voltage transformers, and the nominal device values.
9. 33)0LQ0D[ Minimum and maximum of the real, reactive, and apparent
power, the frequency, and the power factor.
The measured values are converted from secondary to pri-
mary according to the settings entered for the current and
voltage transformers, and the nominal device values.
10.7KHUPDO0HWHU Thermal values from protective functions that calculate
them, such as overload protection, provided such functions
are present.
The percentages given are relative to the tripping tempera-
ture rise for overload protection, and to the maximum allow-
able rotor temperature rise for restart blocking.
11.8VHU'HILQHG Measured values that are defined by the user during initial
setting of the device (see Section 5.2).
12.(QHUJ\ See Sub-section 7.1.3.2.
13.6HW3RLQWV09 See Sub-section 7.1.3.3.
14.5HVHW See Sub-section 7.1.3.4.
If a measured value is not available (for example, thermal values, if the device does
not have thermal protection, or if this protection is set as GLVDEOHG”), then instead
of the measured value, 3 dots appear. If the value is undefined (e.g., cos ϕ, when no
current is flowing), then “---” appears (3 horizontal bars). If a measured value over-
runs, then “
” (3 asteriscs) is displayed.
Use the key to select the measured value group that has the values desired, and
switch to the display of this group with the key. Figure 7-21 shows an example for
the display of operating measured values.