7-337SJ63 Manual
C53000-G1140-C120-1
can also be remotely controlled via binary inputs or the SCADA interface. User-de-
fined logic capabilities offer even more possibilities.
Password No. 5 (password for individual settings) is required to change setting
groups.
The first setting group is called group A. The others are groups B, C, and D. If setting
group changing is to be used, then settings for the groups to be employed must be
entered (see Section 6) and the changeover facility must be (QDEOHG under Address
0103 *US&KJH237,21.
From the
Device Front
When a device is ready for operation, first press the key. The 0$,10(18 appears.
Using the key, select the menu item 6HWWLQJV and switch to the settings with the
key. The selection 6(77,1*6 appears.
Using the key, select the item &KDQJH*URXS and move to the selection of groups
with the key. The sub-menu &+$1*(*5283 appears, as shown in Figure 7-36.
The first Address  is marked. The address displays the setting group presently
in effect (in Figure 7-36, the active group is *URXS$).
Using the key, select Address  and confirm with the key.
Enter the password for individual settings (password No. 5), and confirm.
Using the key, one of the four groups A, B, C, or D can be selected, or control can
be given to another source.
If %LQDU\,QSXW (activation using binary inputs) is selected, setting group
changeover is controlled by binary inputs, provided appropriate masking has been
done and the necessary physical connections are present (see Sub-section 5.2).
If YLD3URWRFRO is chosen, setting group changes can be controlled via the system
serial interface.
Figure 7-36 Changeover Setting Groups from the Operator Control Panel
MENU
ENTER
&+$1*(*5283

$&7,9(*5283
*URXS$
The currently-active setting group is dis-
played under Address .
The setting group can be changed under Ad-
dress : by pressing the key, after
entering the password, two possible alterna-
tives are displayed in a new window each
time:
Using the keys, select one of the alter-
natives and confirm with the key;
The next question ($UH\RXVXUH") is an-
swered with <HV and the selected alternative
is confirmed, or is answered with 1R using the
key and the change is canceled with the
key.
ENTER
ENTER
ENTER
$UH\RXVXUH"
<HV1R
ENTER
&+$1*(WR
!*URXS$
!*URXS$
*URXS%
*URXS&
*URXS'
YLD%LQDU\,QSXW
,(&²²
YLD3URWRFRO