Operators Tools
7-497SJ63 Manual
C53000-G1140-C120-1
6ZLWFKJU,QWORFNHG Refusal because the command object is subject to field interlock-
ing
6ZLWFKLQ3RVLWLRQ Refusal because the present switch position = command direction
6HWWLQJ(UURU Refusal because of a parameter fault, such as unknown command
type
1RW$XWKRUL]HG Command from ON-SITE refused because command object is
subject to switching authority, which is set to REMOTE
&RQWURO([SLUHG Refusal because command is too old (expiry monitor)
1R&RQWURO'HYLFH Information address is not planned as command output
&RQILJ(UURU Refusal because no relay is assigned to this object, or the relay
jumpered in the device does not exist
&RQWURO%ORFNHG Refusal because an output block is set
6\VWHP2YHUORDG" Refusal because a relay to be controlled is already active (e.g., by
another command)
6:WRQHUURU" Refusal because another relay is already controlled
6\VWHP2YHUORDG No more free timers available
8SSHU6HWW/LPLW For transformer LTC step commands, highest level already
reached
/RZHU6HWW/LPLW For transformer LTC step commands, lowest level already reached
([HFXWLQJ&RQWURO New command refused because a command is already in process-
ing
&RPPDQG7LPHRXW Feedback indication missing
%LQDU\,QS,JQRUHG Recording block set
&KDWWHU$FWLYH Flutter block is active
6HWW&KDQJH$FWLYH Refusal because parameter loading process is running
6WDWXV&KDQJH2. Status FRPPDQGH[HFXWHG
6WDWXV&KDQJH)DLO Status command cannot be executed
&KDQJH2. Marking executed
&KDQJH)DLOHG Marking cannot be executed
&KHFNLQJ,QWHUORFN Command is sent to the central unit to check system interlocking
6HWWLQJVDUH2. Parameter change was correctly accepted
7LPH/LPLW([SLUHG Parameter change was interrupted because time expired
7HUPLQDWHG3LFNXS Parameter change interrupted because a fault became active dur-
ing parameterization
5HVWRUH3DUDPHWHUV As a reaction to a fault recognized during parameterization, the last
active parameter set is activated again
3OHDVH:DLW« Initiated process running and requires some time
&KHFNLQJ6HWWLQJV The changed parameters are tested before acceptance
6ZJU)HHGEDFN2. Return message: destination reached
6ZJU)HHGEDFN)DLO Return message: destination not reached
&KDQJH5HMHFWHG Parameter change was rejected (e.g., because time expired, or ab-
normal occurrence during parameterization)
&RQWURO2. Positive conclusion message for commands
9DOXH,QFRUUHFW Plausibility error in command
Table 7-4 Possible Control Messages
Message Text Message Cause