Technical Data
10-38 7SJ63 Manual
C53000-G1140-C120-1
Operating Measured Values
for Power Factor
– cos ϕ
- Range -1 to 1
- Tolerance 5% for |cos ϕ| 0.707
Counter Values for Energy
Wp, Wq (real and reactive energy) in kWh (MWh or GWh) and in kVARh
(MVARh or GVARh)
- Range 8
1
/
2
digits (28 bit) for VDEW protocol
9
1
/
2
digits (31 bit) in T103 mode
- Tolerance 5% for I > 0.5 I
Nom
, V> 0.5 V
Nom
and
|cos ϕ| 0.707
Operating Measured Values
for Frequency
f in Hz (displayed with primary values)
- Range f
N
± 5 Hz
- Tolerance 20 mHz
Operating Measured Values for Θ
S
/Θ
S Trip
Thermal Overload Protection and Θ
L
/Θ
L Trip
Motor Restart Blocking
- Range 0% to 400%
- Tolerance 5% class accuracy per IEC 60255-8
Operating Measured Values for
Sensitive Ground Fault Protection
– I
Ns
, I
Nsa
, I
Nsr
(total, active, and
reactive current) in A or kA primary and in mA secondary
- Range 0 mA to 1600 mA
- Tolerance 2% of measure value or 1 mA
Operating Measured Values for
the Measurement Transducer
- Operating Range 0 mA to 24 mA
- Accuracy Range 1 mA to 20 mA
- Tolerance 1.5% relative to nominal value of 20 mA
For Standard Usage of the Measurement Transducer for Pressure and Temperature
Monitoring:
Operating Measured Value Pressure in hPa
for Pressure
- Operating Range (pre-set) 0 hPa to 1200 hPa
Operating Measured Value Temperature in ºC
for Temperature
- Operating Range (pre-set) 0º C to 240º C
Long-Term Mean
Value
Time Window 15, 30 or 60 minutes
Frequency of Updates adjustable
Long-Term Means of
Currents Ia
dmd
, Ib
dmd
, Ic
dmd
, I
1 dmd
in A (kA)
–Real Power P
dmd
in W (kW, MW)
–Reactive Power Q
dmd
in VAr, (kVAr, MVAr)
Apparent Power S
dmd
in VA, (kVA, MVA)
Min/Max Report Report of Measured Values with date and time