Appendix
A-537SJ63 Manual
C53000-G1140-C120-1
2202 2nd HARMONIC 10..45 % 15 % 2nd. harmonic in % of fundamental
2203 CROSS BLOCK NO
YES
NO Cross Block
2204 CROSS BLK TIMER 0.00..180.00 sec 0.00 sec Cross Block Time
2205 I Max 1.50..125.00 A 37.50 A Maximum Current for Inrush Restraint
3101 Sens. Gnd Fault OFF
ON
Alarm Only
OFF Sensitive Ground Fault
3102 CT Err. I1 0.003..1.600 A 0.050 A Current I1 for CT Angle Error
3103 CT Err. F1 0.0..5.0 ° 0.0 ° CT Angle Error at I1
3104 CT Err. I2 0.003..1.600 A 1.000 A Current I2 for CT Angle Error
3105 CT Err. F2 0.0..5.0 ° 0.0 ° CT Angle Error at I2
3106 VPH MIN 10..100 V 40 V L-Gnd Voltage of Faulted Phase Vph
Min
3107 VPH MAX 10..100 V 75 V L-Gnd Voltage of Unfaulted Phase Vph
Max
3109 64-1 VGND 1.8..130.0 V 40.0 V 64-1 Ground Displacement Voltage
3110 64-1 VGND 10.0..225.0 V 70.0 V 64-1 Ground Displacement Voltage
3111 T-DELAY Pickup 0.04..320.00 sec 1.00 sec Time-DELAY Pickup
3112 64-1 DELAY 0.10..40000.00 sec 10.00 sec 64-1 Time Delay
3113 50Ns-2 PICKUP 0.003..1.500 A 0.300 A 50Ns-2 Pickup
3114 50Ns-2 DELAY 0.00..320.00 sec 1.00 sec 50Ns-2 Time Delay
3115 67Ns-2 DIRECT. Forward
Reverse
Non-Directional
Forward 67Ns-2 Direction
3117 50Ns-1 PICKUP 0.003..1.500 A 0.100 A 50Ns-1 Pickup
3118 50Ns-1 DELAY 0.00..320.00 sec 2.00 sec 50Ns-1 Time delay
3119 51Ns PICKUP 0.003..1.400 A 0.100 A 51Ns Pickup
3120 51Ns TIME DIAL 0.10..4.00 sec 1.00 sec 51Ns Time Dial
3122 67Ns-1 DIRECT. Forward
Reverse
Non-Directional
Forward 67Ns-1 Direction
3123 RELEASE DIRECT. 0.003..1.200 A 0.010 A Release directional element
3124 PHI CORRECTION -45.0..45.0 ° 0.0 ° Correction Angle for Dir. Determination
3125 MEAS. METHOD COS Phi
SIN phi
COS Phi Measurement method for Direction
3126 RESET DELAY 0..60 sec 1 sec Reset Delay
3130 PU CRITERIA Vgnd OR INs
Vgnd AND INs
Vgnd OR INs Sensitive Ground Fault PICKUP criteria
3131 M.of PU TD Multiples of PU Time-Dial
4001 FCT 46 OFF
ON
OFF 46 Negative Sequence Protection