EasyManua.ls Logo

Siemens siprotec 7SJ63 - Page 80

Siemens siprotec 7SJ63
604 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SIPROTEC 4 Devices
4-6 7SJ63 Manual
C53000-G1140-C120-1
The functions of the operating and display elements on the control panel are described
below.
Display Process and device information are displayed in the LCD with a full in graphical dis-
play, or by text. Commonly displayed information includes circuit breaker status, mea-
sured values, counter values, binary information regarding the condition of the device,
protection information, general messages, and alarms.
The light for the display is normally off. The light automatically turns on whenever a
key is pressed on the HMI. If no input from the HMI occurs for ten minutes, then the
light turns off again. The light can be controlled via a binary input that is configured
(programmed) for this purpose.
Keys The keys have various functions.
q
Navigation through the operating menus of the device and movement within the
control display are accomplished with the , , , keys.
q
The main menu is opened with the key.
q
Changes are cancelled or confirmed with the and keys, respectively.
q
Numerical values are entered with the to keys, the key for a decimal
point, and the key for a negative sign. If a value of infinity () is desired, press
the decimal point key twice; appears in the display.
q
The to keys are programmable. The keys are typically used to execute com-
monly performed actions. Labeling strips are provided.
q
Latched LEDs and binary outputs are reset and the group of LEDs are tested with
the key (dual purpose).
LEDs
q
RUN” and “ERROR” LEDs indicate the condition of the device.
q
All other LEDs are freely configured to indicate process information, status, etc. La-
beling strips are provided.
Operating Serial
Interface
Local communication with the device is established through the front operating serial
interface with a PC running DIGSI
®
4. The interface on the device is a 9-pin, female,
D-subminiature port.
Other
(Device Specific)
The operating and display elements above are common in the SIPROTEC
®
4 family.
Some of the devices are equipped with additional operating elements.
q
Control actions can be performed with the On (CLOSE, ) and Off (OPEN, )
keys;
q
Control display can be selected with the key;
Note:
Refer to Section 2 to determine the type of HMI for the specific SIPROTEC
®
4 device.
MENU
ESC
ENTER
0 9
.
+/–
F1 F4
LED
&/26(
23(1
CTRL
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens siprotec 7SJ63

Related product manuals