SIMATIC STEP 7 function blocks
5.2 FB SITOP_PSU8600/SITOP_PSU8600_1
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1, V15 and V15.1 (TIA)
18 Function Manual, 11.2018, A5E37763954-09-76
The procedure for naming the device is slightly different from S7-1200/1500.
The data type HW_IO is not used in S7-300/400.
For more details, refer to the sections
Device_name_PSU8600 (Page 19)
UDT_PSU8600_Data DB for global data exchange.
DB must follow the UDT structure.
Note
The DB attribute "Optimized block access" must be unchecked. To do this, right click on the
global DB in your project in the "Project tree" window and select "Properties". Navigate to
"General >
Attributes", clear the "Optimized block access" check box.
(Reference, symbolic name of the DB for global data exchange)
Note
For S7-300/400
For S7
-1200/1500 controller, it is sufficient to drag the appropriate DB onto the parameter.
-300/400 controllers, the procedure may change.
In the "Cyclic interrupt" window, click on the Data IO parameter field for manual
specification entry.
Select the symbolic name of your data block. A list of global DB contents is displayed.
Select "UDT_PSU8600_Data" data type.