SIMATIC STEP 7 function blocks
5.2 FB SITOP_PSU8600/SITOP_PSU8600_1
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1, V15 and V15.1 (TIA)
20 Function Manual, 11.2018, A5E37763954-09-76
5.2.2
Data type HW_IO for S7-300/400
Data type HW_IO
The data type HW_IO
does not exist in S7-300/400 systems. Data type Word is used here.
The addresses are available in the Hardware (HW) configuration of the respective modules.
1. In the "Device configuration", click "Device view > Device overview" tab.
2. Note down the start address of the SITOP main module (A).
3. Note down the start address of the I/O area of the individual outputs. Skip the PROFINET
interface of the main module (B).
The following addresses for the individual outputs (B and C) are displayed on the screen.
Main module, start address (A): "8186"
Main module cyclic Input address(B): "256"
Cyclic Input address/HW identification address(B) for Output 1, "266"
Cyclic Input address/HW identification address(B) for Output 2, "271"
Cyclic Input address/HW identification address(B) for Output 3, "276"
Cyclic Input address/HW identification address(B) for Output 4, "281"
Main module Cyclic Output address: "256"
Cyclic Output address for Output 1, "264"
Cyclic Output address for Output 2, "272"
Cyclic Output address for Output 3, "280"
Cyclic Output address for Output 4, "288"
Figure 5-4