SIMATIC STEP 7 function blocks
5.7 FB SITOP_PSU8600_Output
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1, V15 and V15.1 (TIA)
Function Manual, 11.2018, A5E37763954-09-76
39
Bool On the rising edge (0 > 1), data at the inputs
of the block is written to PSU/CNX.
HW_IO Start address of the entire main module.
(Reference, system tag: PSU_1 refers to the
assigned PROFINET device name of the
HW_IO Cyclic IO address of output channel.
(Reference, system tag: <PSU Device
Name>~Output_n. For example:
Int Number of the output. (For PSU8600:1 to 4,
Structure of UDT_Output_PSU_IN data type
Int Target voltage of the output in millivolt.
Int Current limit of the output in milliampere.
Pre-alarming threshold (0 to 100 %) for alarming.
Switching the output on/off. (0 = off; 1 = on)
Resetting the output (0 = no reset; 1 = reset)
Byte Operating mode of the output (0 = electronic switch-off
and 1 = constant current)
Switch-on delay of the output. (0 to 60000 ms)