SIMATIC STEP 7 function blocks
5.15 FB SITOP_BAT8600
SITOP PSU8600 Firmware V1.4: Faceplates and Communication Blocks V2.4 for SIMATIC STEP 7 V14 SP1, V15 and V15.1 (TIA)
Function Manual, 11.2018, A5E37763954-09-76
73
Input parameters
Table 5- 61
Parameter
Data type
Description
UPS8600_No
Int
Number of UPS800 to which this battery is connected
Hw_Ident_Head
HW_IO Start address of the UPS8600 submodule (Reference, system
tag: here,
"PSU~UPS8600_V1_4_1~BAT8600_LiFePO4_264Wh_V1_4"
for LiFePO4 battery and
"PSU~UPS8600_V1_4_1~BAT8600_Pb_380Wh_V1_4" for Pb
battery)
Battery_No
Int
Number the plugged BAT8600 module.
Output parameters
Table 5- 62
Parameter
Data type
Description
Battery_Out_Param
UDT_BAT8600_OUT
Number the plugged UPS8600 module.
Structure of UDT_BAT8600_OUT data type
Table 5- 63
Parameter
Data type
Description
Operating_State
Byte
Operating state of the battery.
Calc_Battery_health
Byte
Calculate battery health.
Battery_temperature
Int
Battery temperature
Description of
Operating_state
parameter
Table 5- 64
Status message
Description
0
Off
1
Startup
2
Normal operation
3
Shutdown after error
4
Limited charge
5
End of battery lifetime
6
Battery replacement required
7
Battery replacement completed
8
Battery defective
9 Not ready for buffering
10
Not completely loaded but ready for buffering
11
Ready for buffering
12
Deep discharge recovery

Other manuals for Siemens SITOP series