Additional Installation Instructions
B.3 Magnetic mounting
FSS200 clamp-on sensors
Installation Manual, 08/2017, A5E36255466-AC
103
1. Unpack and disassemble the Magnetic mounting frames.
WARNING
Impact hazard
Magnets may shatter during installation and may cause injury.
KEEP FRAMES SEPARATED (until installation) in order to prevent the magnets from
colliding with excessive force. This may cause the magnets to shatter.
2. The box should contain two Magnetic mounting frames, two sensor clamp plate
assemblies and four C-size sensor spacer plates.
3. Retain all additional sensor spacer plates and their retaining screws, if not used.
WARNING
Pinch hazard
Frame installation may cause Injury to hands.
Exercise CAUTION to avoid pinching hands and fingers when installing the frames in the
desired location, as the frame magnets are very strong.
Required tools
1. Felt marker or grease pencil
2. Tape measure
B.3.2
Preliminary procedures
Pipe and flowmeter setup
1.
Use the Wizard setup procedure to program the transmitter for the sensors that were
selected.
2. After receiving the spacing number index from the transmitter, make a note of the number
displayed.
3. Referring to the transmitter Operating Instructions manual, confirm that the appropriate
sensor settings have been selected for operation on the chosen pipe.
4. Select the mounting location on the pipe.
5. Choose a pipe location that remains full at zero flow.
6. Where possible, locate enclosure housing 10 pipe diameters or more from elbow or valve
to ensure fully developed and stable flow profile.
7. On horizontal pipe sections, select a horizontal plane to avoid sediment or gas blockage
of ultrasonic signal path.