5.4 Sensor wiring
FSS200 clamp-on sensors
Installation Manual, 08/2017, A5E36255466-AC
55
Sensor
User supplied ground wire (see note)
Gland cap nut
Screw, spring washer and U-clamp
Sensor cable
Gland body hex
Sealing gasket
NPT Adapter
Figure 5-4 Cable gland clamp and ground wire
Note
Important
The user supplied grounding wire that is connected to earth ground must be 4mm
2
(10
AWG) or larger.
5.4.4
Preparing RTD sensor cables
RTD Sensor Cable
Note
RTD temperature sensor cables are only available for the FST030.
The temperature sensor cable includes the following:
Optional cable lengths include: 6.1m (20 ft), 15.24m (50ft), 30.48m (100ft), 45.72m
(150ft), 60.96m (200ft) and 91.44m (300ft).
A sealed parts bag that includes an insulating sleeve (15.24cm / 6.0in), crimp lug (for wall
mount RTD ground wire) and 5 crimp lugs for assembling legacy RTD cables, if needed.