7ML19985AN02 SITRANS LU10 – INSTRUCTION MANUAL Page 21
mmmmm
Quick Start Parameters
With the Quick Start Parameters altered as required, proceed to Operation to
With the Quick Start Parameters altered as required, proceed to Operation to With the Quick Start Parameters altered as required, proceed to Operation to
With the Quick Start Parameters altered as required, proceed to Operation to
identify / verify basic system performance.
identify / verify basic system performance. identify / verify basic system performance.
identify / verify basic system performance.
P006 EMPTY
Enter the
maximum distance
(transducer face to vessel bottom) to be measured,
in Units.
This value is preset to 8.000 m (or equivalent Units programmed).
The value entered automatically sets Span (P007) to the maximum
recommended value.
values: 0.000 to 9999
P007 SPAN
Enter the maximum surface distance from Empty (P006).
Span is automatically preset to 1.1 x the blanking value (P800) less than the
Empty value (P006), unless it is altered manually.
For "distance" Operation (P001 = 3), Span is preset to the Empty value (P006).
Enter a lower value if desired. If the automatic setting is not high enough, see
Installation. Always prevent the monitored surface from entering the blanking
zone.
values: 0.000 to 9999