7ML19985AN02 SITRANS LU10 – INSTRUCTION MANUAL Page 47
mmmmm
Enhancement Parameters
Installation Records (P340 to P342)
Use these features to view data relating to this specific SITRANS LU10 installation.
P335 (G) AUTO RECORD B SETPOINT
Enter the critical level which, in conjunction with Auto Record A Setpoint,
defines the boundaries for Auto Profile Records to be saved.
values: -999 to 9999
P336 (G) AUTO RECORD FILLING / EMPTYING
Use this feature to restrict Auto Profile Records from being saved unless the
level is rising, falling or either.
If the level changes at a rate in excess of the corresponding Filling / Emptying
Indicator (P702 / P703) values, the Echo Profile is saved subject to this and other
Auto Profile Record restrictions.
values: 0 = Auto Profile Record on filling or emptying (preset)
1 = Auto Profile Record on filling only.
2 = Auto Profile Record on emptying only.
P337 (G) AUTO RECORD LOE TIME
Use this feature to restrict Auto Profile Records from being saved unless an
extended loss of echo (LOE) condition occurs.
If the LOE condition exceeds the period entered (in seconds) the Echo Profile is
saved, subject to this and other restrictions.
When set for "0" (preset), LOE is not required for an Auto Profile Record to be
saved.
values: 0.0 to 9999
P340 (V) DATE OF MANUFACTURE
View the date of manufacture of this SITRANS LU10.
values: YY:MM:DD format