Page 30 SITRANS LU10 – INSTRUCTION MANUAL 7ML19985AN02
mmmmm
Application Parameters
Failsafe Parameters (P070 to P072)
As preset, in the event of a measurement or technical difficulty, the SITRANS LU10 holds
the Reading, Bar Graph, LU SAM relays (if used) and LU AO mA outputs (if used), at their
last known values.
To operate process control equipment under these conditions, alter the following
parameters as required.
If alternate Failsafe Operation is not required, proceed to RELAY PARAMETERS.
If alternate Failsafe Operation is not required, proceed to RELAY PARAMETERS.If alternate Failsafe Operation is not required, proceed to RELAY PARAMETERS.
If alternate Failsafe Operation is not required, proceed to RELAY PARAMETERS.
P062 OFFSET READING
Enter the value to be added to the Reading, (before display).
This feature is preset to 0.000, (no offset).
e.g. To reference a material level to sea level, enter the distance in Units
(P005), between Empty (P006) and sea level. (Enter a negative value if
Empty is below sea level.)
This feature affects the SITRANS LU10 (and BIC-II, if used) Reading only. (Relays
This feature affects the SITRANS LU10 (and BIC-II, if used) Reading only. (Relays This feature affects the SITRANS LU10 (and BIC-II, if used) Reading only. (Relays
This feature affects the SITRANS LU10 (and BIC-II, if used) Reading only. (Relays
and mA outputs are not affected).
and mA outputs are not affected). and mA outputs are not affected).
and mA outputs are not affected).
values: -999 to 9999
vessel
display offset
(P062)
sea
level
Empty
(P006)