7ML19985AN02 SITRANS LU10 – INSTRUCTION MANUAL Page 61
mmmmm
Enhancement Parameters
SmartLinx Parameters
P750 - P789 PROTOCOL SPECIFIC PARAMETERS
These parameters are specific to the SmartLinx module installed. Refer to
the module documentation for a list and description of the specific
parameter requirements.
P772 BAUD RATE
This feature specifies the rate of communication in Kbaud. Any value can be
entered, but only the values shown are supported.
4.8 = 4800 Baud (preset)
9.6 = 9600 Baud
19.2 = 19200 Baud
38.4 = 38400 Baud
P790 HARDWARE ERROR
Use this feature to display the results of ongoing hardware tests within the
communications circuitry. If any test does not meet the PASS requirements,
communication halts and tests are repeated until PASS requirements are met.
Communication then resumes.
Displays:
PAS S:
FAIL:
ERR1:
no problem
faulty SmartLinx module or SITRANS LU10
unknown protocol, upgrade SITRANS LU10 software
P791 BUS ERROR
This feature indicates if an error condition is occurring on the bus.
Displays: 0 = no error
# = error code, refer to the SmartLinx module documentation for
explanation of the error code
P792 BUS ERROR COUNT
This register increments by 1 each time a bus error (P752) is reported. The
register is factory set at 0 and can be preset to any value. The register is reset to
0 by master reset (P999).