Page 74 SITRANS LU10 – INSTRUCTION MANUAL 7ML19985AN02
mmmmm
Enhancement Parameters
Measurement Parameters (P920 to P923)
Use these parameters to verify Application Parameter programming, when performing a
dynamic material level test over at least 2 empty / fill cycles for each vessel is impractical.
Access the following parameters to take an ultrasonic measurement and:
• display the corresponding Reading in the Parameter Value field.
• set the LU SAM ( if used ) relay status accordingly.
• set the LU AO (if used) mA output value accordingly.
• transmit the corresponding point data to the BIC-II (if used).
If measurements or simulation are desired but the SITRANS LU10 operation has not
If measurements or simulation are desired but the SITRANS LU10 operation has not If measurements or simulation are desired but the SITRANS LU10 operation has not
If measurements or simulation are desired but the SITRANS LU10 operation has not
been verified, disable all associated process control equipment before accessing
been verified, disable all associated process control equipment before accessing been verified, disable all associated process control equipment before accessing
been verified, disable all associated process control equipment before accessing
the following parameters.
the following parameters. the following parameters.
the following parameters.
P911 mA OUTPUT VALUE
Access this parameter to display the current value of the specified LU AO mA
output.
Additionally, this feature may be used to enter a desired value. The mA output is
immediately forced to the value entered regardless of any restrictions
programmed.
values: 0.000 to 25.00
P912 TRANSDUCER TEMPERATURE
Access this parameter to display the vessel temperature in °C (as monitored by
the connected temperature sensing transducer). "Err" is displayed if the
transducer is not equipped with an integral temperature sensor.
values: -50 to 150
P913 SENSOR TEMPERATURE
Access this parameter to display the vessel temperature in °C ( as monitored by
the connected temperature sensor ). "OPEn" is displayed if a TS-3 is not
connected.
values: -50 to 150