7ML19985AN02 SITRANS LU10 – INSTRUCTION MANUAL Page 73
mmmmm
Enhancement Parameters
P905 TRANSMIT PULSE
Press to supply repeated transmit pulses to the transducer and / or view the
transducer operating frequency (automatically altered by (P004) Transducer) for
the Point Number displayed.
This feature may be used to monitor the transmit pulse with an oscilloscope
connected to the transducer terminals.
values: 10.00 to 60.00
P906 COMMUNICATIONS
Press
to test the Siemens Milltronics proprietary communications circuit.
Before activating this feature, connect terminal block contacts 42 to 45 and 43 to 46.
Before activating this feature, connect terminal block contacts 42 to 45 and 43 to 46.Before activating this feature, connect terminal block contacts 42 to 45 and 43 to 46.
Before activating this feature, connect terminal block contacts 42 to 45 and 43 to 46.
On successful test completion, "PASS" is displayed. If "FAIL" is displayed, repeat
the test. (The first test performed sets up the auto polarity function).
P907 PROGRAMMER INTERFACE
Press to activate the programmer interface (two way infrared
communications) test.
On successful test completion, "PASS" is displayed. Otherwise, "FAIL" is
displayed.
P908 SCANNER
Press to activate the scanner test.
When activated, the on board transducer scanning relays energize and de-
energize in sequence.
(The transmit pulse is not supplied to the transducer terminals during this test).
P910 RELAY
Access this parameter to display the current state of the specified LU SAM
relay.
Press to alter the relay state (energized / de-energized) or enter the value
corresponding to the specific relay state desired.
values: 0 = de-energized
1 = energized