Page 40 SITRANS LU10 – INSTRUCTION MANUAL 7ML19985AN02
mmmmm
Application Parameters
P202 mA ALLOCATION
Use this feature if Point Number to mA output allocation alteration is required.
Enter the Point Number(s) the mA output displayed, is to be based upon
As preset, LU AO mA outputs 1-10 are allocated to Point Numbers 1-10
respectively
If two or more Point Numbers are allocated to a single mA output, the output
value represents the Multi-point Average. (The Quick Start Parameter values
should be identical for all points). See
Technical Reference
Application Examples
Example 3 - mA Multi Point Average.
When more than one mA output is allocated to the same Point Number, the mA
Setpoint parameters may be used to establish separate or overlapping mA
output spans. However, the mA Value/Transducer (P203) corresponds to the
lowest mA Output number only.
values: x (x = single Point Number (1-10) to be allocated to the mA output
displayed.
x.y (x = first Point Number (1-10), y = last Point Number (1-10), in the
range)
P203 (V) mA VALUE/TRANSDUCER
View the current value of the mA output associated with the Point Number
displayed.
This is the Auxiliary Reading displayed when is pressed in the RUN mode
and does not include any adjustment made using the 4 or 20 mA Trim (P214,
P215) features.
If the Point Number is included in a mA Multi-point Average calculation, the
displayed value is the average obtained from all Point Numbers included in the
mA Allocation (P202) range.
If more than one mA output is allocated to the same Point Number, the value of
the lowest mA Output Number is displayed.
values: 0.000 to 22.00
mA
5