7ML19985AN02 SITRANS LU10 – INSTRUCTION MANUAL Page 45
mmmmm
Enhancement Parameters
P330 PROFILE RECORD
In addition to serving as a library for profile records, this parameter provides two
functions:
manually records and saves echo profiles
displays an echo profile, recorded manually or automatically, e.g. via an
oscilloscope.
To select a record address:
Press until address index is enabled.
Press or to select the desired address, 1 to 10, and display the
associated parameter value:
‘- - - -’ = no record
‘ x# ’ = record
where: x = A, automatically initiated
= U, manually initiated
# = transducer number
To manually record a profile:
Press transducer* fires and echo profile is recorded into the internal scope
buffer for display.
To save a manual record:
Press to copy the echo profile record in
the scope buffer and save it in the
selected address in in the record
library. The parameter value field
displays the new record ordinates.
To display a record:
Press to copy the echo profile
record in the selected
address to the scope buffer,
for display.
To delete a record:
Press to delete the echo profile
record in the selected
address. Parameter value
returns to ‘ - - - - ’
* Access the Scope Displays (P810) parameter to select the Transducer.
e.g. initial parameter display
e.g address 2 selected, no
record saved
e.g. manually initiated
record from transducder 1
saved in address 2
e.g. oscilloscope displays record
in address 3
e.g.record deleted, address 3
clear