Page 52 SITRANS LU10 – INSTRUCTION MANUAL 7ML19985AN02
mmmmm
Enhancement Parameters
P662 TEMPERATURE SENSOR ALLOCATION
As preset, TS-3 # 1-10 are allocated to Point Numbers 1-10 respectively.
To alter this allocation, enter the TS-3 # whose temperature measurement will
be used for the distance calculation of the Point Number displayed.
When more than one TS-3 temperature sensor is allocated to a Point Number,
the temperature measurements from each sensor are averaged for that vessel.
values: x (x = single Point Number (1-10) to be allocated to the TS-3 # displayed)
x.y (x = first Point Number (1-10), y = last Point Number (1-10), in the
range).
P663 TEMPERATURE TRANSDUCER ALLOCATION
As preset, Ultrasonic/Temperature Transducers 1-10 are allocated to Point
Number 1-10 respectively.
To alter this allocation, enter the Transducer # whose temperature measurement
will be used for the distance calculation of the Point Number displayed.
When more than one transducer is allocated to a Point Number, the temperature
measurements from each transducer are averaged for that vessel.
values: x (x = single Point Number (1-10) allocated to the Transducer #
displayed)
x.y (x = first Point Number (1-10), y = last Point Number (1-10), in the
range).
P664 (V) TEMPERATURE
View the current vessel atmosphere temperature in °C.
This is the value displayed when is pressed in the RUN mode.
If Temp Source (P660) is set to any value other than Fixed Temp, the value
displayed is the temperature measured. If Temp Source is set to Fixed Temp, the
P661 value is displayed.
values: -50 to 150
6