7ML19985AN02 SITRANS LU10 – INSTRUCTION MANUAL Page 91
mmmmm
Technical Reference
Example 4 - Distance Measurement
This mode of operation may be used for equipment position monitoring up to 60 m (200 ft).
Operation is similar to Space Measurement operation except that measurements are
referenced to the transducer face.
For this example we’ll assume the following:
Transducer 10 (an XLS-60) is mounted horizontally* facing the Tripper Car.
when the Tripper Car is at the far end stop, the transducer face to Tripper Car
distance is 175 ft.
when the Tripper Car is at the near end stop, the transducer face to Tripper Car
distance is 5 ft.
the Tripper Car travels at 7 ft/min, and is normally maintained 14 ft from either
end stop.
a mA output proportional to Tripper Car distance from the transducer is required
for PLC operation.
if the PLC reads 3.8 mA, the Tripper Car is to immediately stop.
an LU AO is connected to the SITRANS LU10 Peripheral Communications
terminals.
*When an XLS or XLT series transducer is mounted horizontally, install a support plate
under the transducer to prevent possible mounting/conduit connection damage.
175 ft
5 ft
XLS-60
transducer
support
plate
to