Page 18 COMMUNICATIONS FOR SITRANS LUT400 (HART) – MANUAL A5E33701270
mmmmm
Operation - PDM
a. Enter the desired Level and Volume values, and click on OK.
c. Back in the Step 4 of 5: Ranges window, click on NEXT.
Step 5 - Summary
1. Check parameter settings, and click on Cancel to abort, or apply your changes.
2. Click Apply to save your changes and return to the main menu, or click Apply and
Transfer to save your changes and transfer settings to the device.
The message Quick Setup was successful will appear. Click on OK.
Configuration via SIMATIC PDM Quick Start Wizard for a Volume application with a
complex vessel shape is now complete.
Notes:
• The Reset button resets values to the values in the offline table.
• When entering breakpoints via the wizard, values should be entered from the
bottom to the top of the vessel so that the characterization chart accurately
reflects values as they are entered.
• To add points for Level and Volume equal to 0, enter these points first.
• When using a linear table, add at least two points.
• When using a curve table, add at least four points.
• If entering or modifying breakpoints via the parameter menu (after initial wizard
is complete), ensure
2.6.1.Vessel Shape
is set to Linearization Table prior to
level/volume values being transferred, otherwise two uploads must be
performed:
a) one to read Linearization Table as enabled,
b) and one to transfer breakpoint values.