Building Technologies Basic documentation: Communication via the KNX bus CE1P3127en
HVAC Products Engineering notes 30.08.2007
100 m
N1
N4
3127Z03en
N2
200 m
100 m
100 m400 m
Distance between
bus devices max. 700 m.
Not allowed:
N1 to N4 = 900 m
N2 to N4 = 800 m
N3
100 m
250 m150 m
Distance between bus device
and bus supply max. 350 m.
Not allowed: N4 = 550 m
PSU
N1 .. N4 Bus devices
Bus device N4 – while adhering to the maximum distance of 700 m between bus
devices – cannot be integrated on the bus if bus device N3 is integrated with a loop
(instead of a sub-line).
If a maximum distance of 350 m is maintained between the central bus power
supply PSU and a bus device without a bus supply, the bus power supply unit must
be located at the point between 150 m and 250 m on the 400 m section shown.
100 m
N1
N4
3127Z04en
N2
200 m
100 m
100 m400 m
N3
200 m
100 m
N5
Total lenght
max. 1000 m,
exceeded by
N5
N1 .. N5 Bus devices
With the bus wiring shown, the integration of device N5 on the bus causes the
permissible total length of 1000 m to be exceeded.
Example 1
Distances
Example 2
Total length