Building Technologies Basic documentation: Communication via the KNX bus CE1P3127en
HVAC Products Large plants 30.08.2007
8.1.2 IP router as a coupler to the IP network
The router can be connected via to the IP network via Ethernet cable and the
integral RJ45 socket of the IP router.
1.1.0
1.1.1
1.1.2
1.1.x
1.2.0
1.2.1
1.2.2
1.2.x
192.168.10.1
255.255.255.0
N146
1.0.0
10BaseT
KNX
N140/13 N140/13
3127Z08en
IP Network (Area line 0)
Cat5 cable
Main line 1
Lc
IP Ac
Lc
Line 1
Line 2
The IP router has a 10BaseT interface (Ethernet at 10 Mbit/s via Cat5 cable).
When using IP routers, the following rules must be observed:
With an IP router used as an area coupler (IP Ac)
no other IP routers may be
installed below
the IP Ac in the topology.
With an IP router used as a line coupler (IP Lc)
no other IP routers may be
installed above
the IP Lc in the topology.
When IP routers are used for coupling to an IP network, the following points must
be discussed with the IP network administrator:
Automatic address assignment via DHCP (see section 8.3)
or
Manual IP address assignment (see section 8.3)
and also:
IP routing, multicast addresses
IP subnet mask
IP standard gateway
This document does not deal with the technical aspects of Ethernet