80/120
Building Technologies Basic documentation: Communication via the KNX bus CE1P3127en
HVAC Products Large plants 30.08.2007
KNX network with third-party devices in Area 15
1.2.1
1.1.1
RM...
1.1.2
RM...
1.1.250
RM...
1.2.2
RM...
1.2.250
RM...
RM...
1.15.1
RM...
1.15.2
RM...
1.15.250
RM...
N140/13
1) 1)
N140/13
1)
N140/13
N140/13
1)
1.0.1
RM...
RM...
1.0.2
1.0.250
Bereich 0
0.2.150
OZW775
1)
2.0.1
RMB...
2.0.10
RX...
RX...
2.0.20
RX...
2.0.250
N140/13
0.2.254
-12 °C
-12 °C
3)
N140/13
N125/x1
15.0.10
Dimmer
15.0.20
2)
N140/13
15.1.10
0.2.252
RMZ792
15.0.1
AC 120...230 V
~
N125/x1
15.1.1
AC 120...230 V
~
Line 1
Line 2
Line 15
Main line 1
ACS alarm
pager, SMS, fax
Main line 2
PC with ACS
Service cable
RJ45
connector
Bus connector
socket
Bus power supply
Input and
display unit
Input and
display unit
Line 1
Main line 15
Switch
actuator
3127Z44en
Bus power supply
Switch
actuator
Ac 1.0.0 Ac 2.0.0
Ac 15.0.0
Lc 1.1.0 Lc 1.2.0
Lc 1.15.0 Lc 15.1.0
LTE filter table: 1) Normal (route), 2) Route all, 3) Block all
If the filter is set to "Block all" for area coupler Ac 15.0.0, no LTE telegrams are
transmitted between area 15 and the rest of the network.
The "Route all" setting for line coupler Lc 15.1.0 means that there is no filtering
between line 15.1 and main line 15.
If the devices in area 15 (e.g. third-party products) do not supply power to the bus,
an N125/x1 power supply unit must be installed in each line (main line 15, line 15.1
plus further lines 15.x, if applicable) for the bus power supply.
Example 3
LTE filter table
Bus power supply