Building Technologies Basic documentation: Communication via the KNX bus CE1P3127en
HVAC Products Appendix 30.08.2007
9.2.2 Changeover via analog input
The outside temperature sensor is wired to universal input "x"(configured as an
analog input) of the "H/C changeover" function block in controller 1 (RMU7x0B).
The release relay in controller 1 affects the generation of heating/refrigeration
energy. The heating/cooling changeover signal affects all controllers (in this case
controller 1 and controller 2) in the same heating/refrigeration distribution zone.
If the source of the H/C changeover is an analog signal, then two limit values must
be selected for the changeover. For further information refer to the basic
documentation, manual P3150.
1
M
T
1
KNX
2
M
2
T
T
2
S1 S1 S1
S2 S2
x
S2
S3
QY
d
123
9
x
ltebedarf
QY
d
S4 S4 S4
S5
123
9
x
Q
23
9
1
S1 S1 S1
S2 S2
x
S2
S3
QY
d
123
9
x
ltebedarf
QY
d
S4 S4 S4
S5
123
9
x
Q
23
9
T
AI
Htg/ClgCoil 1 Htg/ClgCoil 2
3127S04en
Flow
Return
H/C changeover signal
Heat/refrig distribution zone 1
H/C changeover
Heat demand
Supervision Controller
Controller
Supervision
Refrig demand
H/C changeover
Heat demand
Supervision
Controller
Controller
Supervision
Refrig demand
Changeover source
analog input AI
Note