67/120
Building Technologies Basic documentation: Communication via the KNX bus CE1P3127en
HVAC Products Communication via zone addresses 30.08.2007
7 Communication via zone addresses
7.1 General notes on zones
7.1.1 Synco zoning
Zoning in Synco is based on KNX and covers the following zones for Synco 700
devices and RXB/RXL room controllers:
Designation
RMU
RMH
RMK
RMB
RMS
QAW
RXB
RXL
Zone
address
range
Def'
value
RM...
Def.
value
RX…
Geographical zone (apartm) x x x x x x x x 1…126 ---- /1 ----
Geographical zone (room) x x x x x 1…63 * ---- /1 1
Geographical zone (subzone)
x x 1…15 * 1
Time switch zone (apartment)
x x 1…126 1
Time switch zone (room)
x x 1…63 * 1
Time switch zone (subzone)
x x 1…15 * 1
Time switch slave (apartment) x x x x 1…126 ---- /1
Master/slave zone (apartment)
x x 1…126 1
Master/slave zone (room).
x x 1…63 * ----
Master/slave zone (subzone)
x x 1…15 * 1
QAW op.zone (apartment)
x 1…126 ----
Heat distribution zone x x x 1…31 1
Heat distr zone source side x x x x 1…31 ----
Heat distr zone consumer side x x x 1…31 1 / 2
Heat distr zone heating surface
x x 1…31 ----
Heat distribution zone air heater
x x 1…31 ----
Heat distrib. zone, primary distr.
x
1…31 1
Heat distrib. zone, primary contr.
x 1…31 2
Refrigeration distribution zone x x 1…31 1
Refrig distr zone source side x x x 1…31 ----
Refrig distr zone consumer side x x 1…31 ---- /1
Refrig distr zone cooling surface
x x 1…31 ----
Refrig distrib. zone cooling coil
x x 1…31 ----
Air distribution zone x 1…31 1
Boiler sequencing zone
x 1…16 1
DHW zone
x 1…31 1
Holiday/special day zone x x x x x 1…31 ---- /1
Time switch, DHW slave
x 1…31 1
Outside temperature zone x x x x x x x 1...31 ---- /1 1
Solar zone
x 1...31 ----
Wind zone
x 1...31 ----
---- / 1 Depending on the device, the default is "----" (e.g. RMU7x0B) or "1" (e.g. RMU7x0).
See also section 7.1.4 for information on the default "----" with the series B devices.
---- With RXB/RXL room controllers "----" indicates that the zone is "out of service" and there are no
process values transmitted from this zone (in the QAX34.3 room device, "-1" is displayed
instead of "----".
* The zone address range for the RXB/RXL room controllers is 0…63 or 0…15.
Zones and devices