72/120
Building Technologies Basic documentation: Communication via the KNX bus CE1P3127en
HVAC Products Communication via zone addresses 30.08.2007
7.2 Zone addressing with the RMZ operator units
7.2.1 RM… controllers
For the Synco 700 type RM… controllers, the zone addresses can be set with the
RMZ790 and RMZ791 operator units. The zone addresses can be set without a
commissioning tool, also referred to as "Easy configuration".
Access at the Password level
takes the user to the operating pages and
operating lines.
To set the zone address, use the following path to the "Room" operating page:
Main menu > Commissioning > Communication > Room
Turn the rotary knob to select the "Geogr zone (apartm)" line.
Turn the knob as required for access to setting mode.
In setting mode, set the zone address rotating the knob as required.
Introduction
Setting procedure
Step 1
RM…controllers
RM…B controllers
Step 2
RM…controllers
RM…B controllers
Step 3
Room
Geogr. zone (ap.): 1
Time switch op: Autonom
TS slave (apart.): 1
Geographical zone (apartment)
1
1
126
└┴┴┴┴┴┴┴┴┴┴┴┴┴┴┴┴┘
Geographical zone (apartment)
5
1
126
└┴┴┴┴┴┴┴┴┴┴┴┴┴┴┴┴┘
Room
Geogr. zone (ap.): ----
TS slave (apart.): ----
Time switch op: Autonom
Geographical zone (apartment)
----
1
126
└┴┴┴┴┴┴┴┴┴┴┴┴┴┴┴┴┘