EasyManua.ls Logo

Siemens Synco RMU730 - Filtering, Zone Addresses, Communication Areas

Siemens Synco RMU730
120 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
86/120
Building Technologies Basic documentation: Communication via the KNX bus CE1P3127en
HVAC Products Large plants 30.08.2007
8.2.3 Filtering, zone addresses, communication areas
The diagrams below show the relationship between filter settings, zone addresses
and communication areas, based on the zone addresses for distribution zones.
Prerequisite: All area/line couplers and IP routers in the network must have the
same filter setting.
LTE telegrams with zone addresses 1…15 are communicated only within the line,
i.e. telegrams with these zone addresses are blocked.
LTE telegrams with zone addresses 16…31 are communicated outside that line, i.e.
telegrams with these zone addresses are routed.
Z'addr.
1...15
3127Z46en
Zone addr. 16...31
Normal (route)
Z'addr.
1...15
Z'addr.
1...15
Zone addresses that are blocked by the filter setting "Normal (route)" can be re-
used in other KNX areas and lines, but only if the attribute "Normal (route)" is valid.
All LTE telegrams with zone addresses 1…31 are communicated throughout the
network (no filtering).
Z'addr.
1...31
Z'addr.
1...31
Z'addr.
1...31
3127Z47en
Zonen addr. 1...31
Route all
Normal (route)
Note
Route all

Table of Contents